[[ CONTINUOUS MEASUREMENT l DETECTION ]]

Admittance - Hycontrol Admittance level switches

HYCONTROL CAPACITIVE LEVEL SWITCH RANGE

Hycontrol ME capacitive level switches provide simple, accurate and reliable level control for a wide range of applications. They are suitable for use on liquids, solids, slurries, pastes, granules, powders and pellets in high temperature, high pressure and corrosive environments.
Unlike some other capacitive switches, this unit works independently of the tank walls using an integral grounding sleeve without the need for a reference probe, which enables it to be used in concrete, plastic or other non metalic tanks.
This technology also provides an ideal solution for interface detection applications such as oil on water and liquid detection underneath a layer of foam.

 

CAPACITIVE SWITCH FEATURES

• Easy installation through a 1” BSP process fitting
• High corrosion and chemical resistance as standard options
• Universal design can be used for high or low level detection
• Multiple versions with rod and cable to simplify mounting options
• High temperature versions up to 800 C
• Low maintenance technology with no moving parts
• Hazardous area certified versions ATEX approved
• Adjustable sensitivity for a wide range of products
• Adjustable time delay to stop spurious signals from surface ripple
• Anti-static probes for plastic pellet applications with high static probability
• Remote electronics option for high vibration applications
• Interface level detection for difficult applications

 

CONSTRUCTION

1. Probe : 304SS or 316SS
2. Insulation : UPE or PTFE
3. Grounding Sleeve : 304SS or 316SS
4. Connection : 1" BSP standard
5. Housing : Aluminum IP65 epoxy coated

6. Conduit entry : " BSP
7. Housing O-Ring : NBR
8. PC board : A, B, C, D Type
9. Sensitivity adjustment : 10pF, 20pF, 40pF
10. Cover : Aluminum epoxy coated

 

STANDARD GENERAL PURPOSE VERSIONS

Dimension

Model

ME10 A/B/C

[STANDARD TYPE]

ME11 A/B/C

[ STANDARD TYPE]

ME20 A/B/C

[ HI-TEMP. TYPE ]

Operating Temp.

-20C~80C

-20C~80C

-20C~200C

Probe Material

304SS

304SS

304SS

Insulation Material

UPE

UPE

PTFE

Connection

1"BSP

1"BSP

1"BSP

Sensitivity Range

10pF, 20pF, 40pF

10pF, 20pF, 40pF

10pF, 20pF, 40pF

Weight

Approx. 1.9kg

Approx. 1.9kg

Approx. 2.4kg

Enclosure Details

Aluminum IP65

Supply Voltage

110/220VAC 10% or 24VDC

Delay Time

0~6 seconds

Power Consumption

2W

Contact Rating

5A/240VAC or 5A/30VDC, SPDT or NPN 100mA

 

HIGH TEMPERATURE AND CORROSION RESISTANT VERSIONS

Dimension

Model

ME28 A/B/C

[ HI-TEMP. ]

ME30 A/B/C

[CORROSION-PROOF]

ME32 A/B/C

[ CORROSION-PROOF ]

Operating Temp.

-20C~800C

-20C~80C

-20C~200C

Probe Material

304SS

304SS

Wetted part: PVDF coating

Insulation Material

CERAMIC

Wetted part: PVDF coating

UPE

Connection

2"x5kg/cm2 JIS Flange

1-1/2"x10kg/cm2 JIS Flange (UPE)

1-1/2"x10kg/cm2 JIS Flange (SS) with PVDF Washer (5mm)

Sensitivity Range

10pF, 20pF

10pF

10pF, 20pF

Weight

Approx. 6.5kg

Approx. 2kg

Depends on the length

Enclosure Details

Aluminum IP65

Supply Voltage

110/220VAC 10% or 24VDC

Delay Time

0~6 seconds

Power Consumption

2W

Contact Rating

5A/240VAC or 5A/30VDC, SPDT or NPN 100mA

 

REMOTE AND CABLE VERSIONS

Dimension

Model

ME40 A/B/C

[REMOTE PROBE TYPE]

ME50 A/B/C

[ WIRE-PROBE TYPE]

ME60 A/B/C

[ PLATE TYPE ]

Operating Temp.

-20C~100C

-20C~80C

-20C~80C

Probe Material

304SS

304SS cable

304SS

Insulation Material

UPE

UPE

UPE

Connection

1"BSP (SS)

1"BSP (SS)

2-1/2"x5kg/cm2 JIS Flange (SS)

Sensitivity Range

10pF

10pF, 20pF, 40pF

10pF, 20pF, 40pF

Weight

Approx. 3kg

Approx. 4.1kg

Approx. 3.2kg

Enclosure Details

Aluminum IP65

Supply Voltage

110/220VAC 10% or 24VDC

Delay Time

0~6 seconds

Power Consumption

2W

Contact Rating

5A/240VAC or 5A/30VDC, SPDT or NPN 100mA

 

INTRINSICALLY SAFE VERSIONS FOR HAZARDOUS AREAS

Dimension

Model

ME70D (with EX-75)

[STANDARD TYPE]

ME72D (with EX-75U)

[ HI-TEMP. TYPE]

ME75D (withEX-75U)

[ WIRE PROBE TYPE ]

Operating Temp.

-20C~80C

-20C~200C

-20C~80C

Probe Material

304SS / 316 SS

304SS / 316 SS

304SS / 316 SS cable

Insulation Material

PTFE or UPE

PTFE or UPE

PTFE or UPE

Connection

1"BSP (SS)

1"BSP (SS)

1"BSP (SS)

Sensitivity Range

10pF, 20pF, 40pF

10pF, 20pF, 40pF

10pF, 20pF, 40pF

Weight

Approx. 1.9kg

Approx. 2.4kg

Approx. 4.1kg

Enclosure Details

Aluminum IP65

Supply Voltage

16~24VDC

Enclosure Protection

ATEX EEx ia iiC (*)

Power Consumption

2W

Contact Rating

NPN 100mA

 

INTRINSICALLY SAFE VERSIONS FOR HAZARDOUS AREAS

Dimension

Model

ME76D (with EX-75)

[PLATE TYPE]

ME77D (with EX-75U)

[ ANTI-STATIC TYPE] HI-TEMP.

ME78D (withEX-75U)

[ ANTI-STATIC TYPE ]

Operating Temp.

-20C~80C

-20C~200C

-20C~80C

Probe Material

304SS / 316 SS

PTFE or UPE coating

PTFE or UPE coating

Insulation Material

PTFE or UPE

PTFE or UPE

PTFE or UPE

Connection

2-1/2"x5kg/cm2 JIS Flange (SS)

1"BSP (SS)

1"BSP (SS)

Sensitivity Range

10pF, 20pF, 40pF

10pF, 20pF

10pF, 20pF

Weight

Approx. 3.2kg

Approx. 3.1kg

Approx. 2kg

Enclosure Details

Aluminum IP65

Supply Voltage

16~24VDC

Enclosure Protection

ATEX EEx ia iiC (*)

Power Consumption

2W

Contact Rating

NPN 100mA

 

ANTI-STATIC AND TEFLON PROBE VERSIONS

Dimension

Model

ME80 A/B/C

[ANTI-STATIC TYPE]

ME81 A/B/C

[ ANTI-STATIC TYPE] HI-TEMP.

Operating Temp.

-20C~80C

-20C~200C

Probe Material

UPE coating

PTFE coating

Insulation Material

UPE

PTFE

Connection

1"BSP (SS)

1"BSP (SS)

Sensitivity Range

10pF, 20pF

10pF, 20pF

Weight

Approx. 2kg

Approx. 2.5kg

Enclosure Details

Aluminum IP65

Supply Voltage

110/220VAC 10% or 24VDC

Delay Time

0-6 seconds

Power Consumption

2W

Contact Rating

5A/240VAC or 5A/30VDC, SPDT or NPN 100mA

 

HAZARDOUS AREA INTRINSICALLY SAFE VERSION

EX-75U Zener barrier provides intrinsic safety to the ME7D type level switch by limiting the current from the control module in the safe area to the level switch in the hazardous zoned area.Please contact the office for a copy of the certificates and more information if required.

1. Supply voltage :

110 / 220VAC

2. Power consumption :

2W

3. Input signal :

NPN transistor

 

resistance Ri= 500W

4. Output voltage :

16~24 VDC

5. Short circuit current :

25mA max.

6. Relay output :

SPDT

 

10A /30VDC

 

10A /220VAC

7. Operating temp. :

-20C ~ 60C

8. Weight :

0.3 kg

9. Enclosure mounting :

DIN Rail

 

ADJUSTMENT

COARSE CALIBRATION

With the probe in contact with the material being detected, set the SENSITIVITY ADJ pointer to position H and then using a blade screwdriver set the COARSE adjustment until the INDICATOR lamp is on. Rotating the COARSE adjustment clockwise and counter-clockwise will turn the INDICATOR lamp on and off. Ensure the lamp is on before moving on to adjusting the sensitivity.

000

DELAY FUNCTION SETTING

This feature is used to stop any spurious signals to the switch from surface ripple or agitation of the product. It also protects the relay from premature wear by eliminating contact chatter by adding a small time delay from when product contacts the probe .

The factory setting is zero seconds with the DELAY screw fully counter clockwise.
Turning the screw in a clockwise direction introduces a delay between the INDICATOR lamp coming on and the relay changing its state.

 

SENSITIVITY ADJUSTMENT

After setting the COARSE calibration the INDICATOR lamp will switch on when probe is touching the material and off when in free air.
Make sure the probe is in contact with the material and then turn the SENSITIVITY ADJ knob clockwise until the INDICATOR lamp turns off. Set the SENSITIVITY ADJ pointer half way between H and the point that the INDICATOR lamp switches off.

 

 

 

INSTALLATION GUIDE

 

 

 

The grounding sleeve must be mounted to protrude at least 30mm from the vessel wall.

For the ME60 type to be mounted properly the vessel walls should not exceed 25mm thickness.

To prevent false readings on solids applications it is best to make sure the material flows symmetrically. If the inlet is not located in the centre portion of the tank roof, check the flow pattern (a angle) of your material and place the probe in the
Appropriate location.

If the probe is mounted on the top, make sure the length of probe is enough to touch the highest level of raw material.
The ME50 type must have at least 300mm from the silo wall.
The ME60 type is usually
Located at the lower position
.

For Non-Stationary or material that will be vibrated a separate control unit such as the ME40 type is recommended.

Where possible install the probe away from the inlet to reduce the risk of inflowing material damaging the probe. If the probe is near an inlet, we recommend placing a protective cover 200mm above the probe. The cover should be parallel to the probe and the same length .

 

 

 

If multiple probes are mounted
In the same vessel they must be separated by at least 300 mm to reduce probe to probe interference .

The probe should not be mounted underneath a liquid inlet otherwise it will switch on erroneously.

If the tank is equipped with an agitator, please use the time-delay function to stop spurious signals

The cable inlet should face downward to avoid rainwater ingress.

Mounting the probe at a 20 incline optimizes the results and increases the switch sensitivity.

Mounting the probe at top of tank will help avoid material bridges from forming and reduce false alarms.

 

ORDER INFORMATION

 

•Tolerance of the total product length is 5mm.
•Characteristics, specifications and dimensions are subject to change without notice.
•Please contact Hycontrol if you have a special request not mentioned in the above

 

Hycontrol Level switches with this option have an additional pair of terminals provided in the switch head that simply require a push button switch to connect these two terminals together and this is usually mounted at ground level local to the silo fill point.

After pushing this button the circuit is then loaded as if a product has touched the active part of the probe and the electronics (if working correctly) will detect this change in capacitance and activate the relay to change its state. Any audio or visual alarms wired to this relay will then be activated and will continue until the ground level test button is released. If the test is successful then the operator can then proceed to fill the silo, confident that the high alarm will operate if required to do so.

Hycontrol provide a complete alarm and test panel solution for single or multipoint applications however a simple push button can easily be retrofitted to existing panel installations with little or no disruption to the plant operations providing the alarms and sirens already exist!

This ground level test facility is offered as an option on Hycontrol’s range of capacitive, admittance and vibrating level swiches.