[[ CONTINUOUS MEASUREMENT l DETECTION ]]

Admittance - Hycontrol Admittance level switches

 

PRODUCT INTRODUCTION

The Hycontrol range of Admittance level switches provide simple, accurate and reliable level
control for a wide range of applications. They are suitable for use on liquids, solids, slurries,
pastes, granules, powders and pellets in high temperature, high pressure and corrosive
environments.
The main advantage offered by using this admittance range of switches is their ability to totally
ignore product build up on the sensing probe.
This unique design utilises a protective insulation electrode between the conventional main
electrode and the grounding sleeve which enables the electronics to distinguish between
coatings and actual product level.
This technology also provides an ideal solution for interface detection applications such as oil
on water and liquid detection underneath a layer of foam.

SWITCH FEATURES

Unaffected by material coating on the sensing probe

No moving parts to wear out

Easy installation through a 1” BSP process fitting

High corrosion and chemical resistance as standard options

Universal mounting for high or low level detection

Multiple versions with rod and cable to simplify mounting options

High temperature versions available

Low maintenance technology with no moving parts

Hazardous area certified versions ATEX approved

Adjustable sensitivity for a wide range of products

Adjustable time delay to stop spurious signals from surface ripple

Remote electronics option for high vibration applications

Interface level detection

High and low failsafe selection options

 

TYPICAL APPLICATIONS

Acid Tanks and silos

Bitumen, Tar and Asphalt

Adhesives, Polymers and Paints

Syrups and pastes

Powders ,flakes and granules

 

CONSTRUCTION & APPLICATION

Construction

1.

Main Contact Probe:

 

SUS304 or SUS316 Material

2.

Main Insulation Probe:

 

Insulation of main Probe and reference

 

current, made of either PTFE or PFA.

3.

Reference Current:

 

Conductive metal probe to dissipate

 

any possible presence of false signal.

4.

Insulation Probe:

 

To protect contact probe and external

 

insulation probe, having very low

 

current inducing characteristics and is

 

made of either PTFE or PFA.

5.

Process Connection:

 

1"BSP (Standard model)

6.

Housing:

 

Aluminum Alloy with paint finish

7.

Electrical Entry:

 

1/2" NPT

8.

Housing seal:

 

Buna N ‘O’ Ring

9.

Time Delay:

 

FSH and FSL, Time Delay Adjustable

 

function

10.

Housing Cover:

 

Aluminum Alloy Spray Paint

 

Industry Applications

Brewery Plant

Mining Plant

Chemical Plant

Paper Manufacturing Plant

Cement Plant

Medical Plant

Coal Plant

Power Plant

Food Processing Plant

Water and Waste Water

Flour Mill

 

Treatment Plant

Glass Industry

Tar Factory

Paint Plant

Beverage Plant

Plastics Plant

Bitumen Coating Plant

Quarrying Plant

Dairy Plant

Aggregate Plant

Automotive Plant

 

SPECIFICATION

 

Dimension
(mm)

Model.

MD49 [Separation Model]

MD50 [CableModel]

MD60 [Mini Model]

Operating Temp.

-40°C 150°C,MAX 550°C ~

-40°C 150°C ~

-40°C 150°C ~

Ambition Temp.

-40°C 65°C ~

-40°C 65°C ~

-40°C 63°C ~

Housing

Stainless (IP65)

Aluminium (IP65)-seperation

Aluminium (IP65)

Aluminium (IP65)

ProbeMaterial

304SS or 316SS

304SS or 316SS

304SS or 316SS

Insulation

PTFE or PFA

PTFE or PFA

Ceramic

Connection

3/4" BSP

3/4" BSP

3/4" BSP

Sensitivity

0.3PF

0.3PF

0.3PF

Supply Voltage

110/220VAC 10% +

50/60HZ

110/220VAC 10% +

50/60HZ

110/220VAC 10% +

50/60HZ

Power Consumption

2.3 W

2.3 W

2.3 W

Contact Rating

5A/250VAC, DPDT

5A/250VAC, DPDT

5A/250VAC, DPDT

Delay Time

0~90 sec

0~90 sec

0~90 sec

Fail safe mode

High / low

Selectable

High / low

Selectable

High / low

Selectable

Conduit

1/2" NPT x2 hole

0

0

Operation Pressure

20kg/cm2

20kg/cm2

20kg/cm2

Weight

0

Depend on cable length

0

WIRING DIAGRAM

• Ensure the power supply is shut off
• Pull the power lines through the cable inlet into
the housing


• Power supply voltage could be selected at 110V
or 220V, but the live wire must be connected to
their respective terminals, 110V live wire to 110V
terminal, 220V live wire to 220V terminal. The
neutral line can be connected to 0V terminal and
the ground line is to be connected to the GND
terminal


• Relay output connection:
Relay outputs are set at SPDT or DPDT,
maximum switching current and voltage is
5A/250VAC, able to drive small loads such as:
solenoid valves, alarm sirens, etc. Bigger loads
requires larger relay to drive it. The diagrams
below and on the right are common examples of
wiring methods.


Fail safemode :


Fail safe mode is used primarily to detect
malfunction situations. Example: Power
supply disruptions, causing the relay to lose
it's driving voltage, this type of situation is
called fail safe, meaning that in cases of
black out, there will be an alarm signal. The
fail safe mode “FSH" and "FSL" selection is
dependent on the installation position of the
probe, the table below shows the fail safe
conditions of each mode:

ORDER INFORMATION

 

Hycontrol Level switches with this option have an additional pair of terminals provided in the switch head that simply require a push button switch to connect these two terminals together and this is usually mounted at ground level local to the silo fill point.

After pushing this button the circuit is then loaded as if a product has touched the active part of the probe and the electronics (if working correctly) will detect this change in capacitance and activate the relay to change its state. Any audio or visual alarms wired to this relay will then be activated and will continue until the ground level test button is released. If the test is successful then the operator can then proceed to fill the silo, confident that the high alarm will operate if required to do so.

Hycontrol provide a complete alarm and test panel solution for single or multipoint applications however a simple push button can easily be retrofitted to existing panel installations with little or no disruption to the plant operations providing the alarms and sirens already exist!

This ground level test facility is offered as an option on Hycontrol’s range of capacitive, admittance and vibrating level swiches.

 

HYCONTROL LEVEL TECHNOLOGIES